Standards and Specifications
|
IEC-61439-1, 2, IEC 60529
|
Rated impulse withstand voltage (Ui)
|
9.8kV / 8 Kv
|
Rated Insulation voltage (Ui)
|
1000 V
|
Rated Operational voltage (Ue)
|
690 V
|
Rated Currents (In)
|
Main horizontal busbars
Rated current (In)
Rated Peak withstand current (Ipk) Rated
Short-time withstand current (Icw)
|
up to 3200A
up to 187kA
up to 85kA/1s
|
Vertical busbars fixed system
Rated current (In)
Rated Peak withstand current (Ipk) Rated
Short-time withstand current (Icw)
|
up to 1600A
up to 150kA
up to 70kA/1s
|
Vertical busbars Removable & Withdrawable system
Rated current (In)
Rated Peak withstand current (Ipk)
Rated Short-time withstand current (Icw)
|
up to 1600A
up to 100kA
up to 50kA/1s
|
Internal seperation
|
Form 1 to 4
|
Degree of Protection
|
IP2X up to IP44
|
Colour
|
RAL 7032, 9035
|
Materials
Doors & Plates
Framework
Plinth
Mounting Plates
Internal Plates
Stainless Steel (optional)
Rear Plates
Top Plates
|
Painted Steel 1.5mm or 2.0mm
Painted Steel 2.0mm
Painted Steel 2.5mm
Steel sheet 2.0mm
Steel sheet 1.0mm
ANSI 304 160/80
Steel sheet 1.5mm
Steel sheet 1.5mm
|
Dimensions (mm)
|
Height: 1995, 2185, 2375
Width: 380, 570, 760, 950, 1140
Depth: 600, 790
|