Electrical characteristics
|
Rated insulation voltage Ui (V AC)
|
1000
|
Rated operation voltage (V AC)
|
690
|
Rated impulse withstand voltage (KV)
|
12
|
Frequency (Hz)
|
50/60
|
Main busbar rated current max. Ie (A)
|
3200 / 4000
|
Rated short-time withstand current Icw (KA / 1 s)
|
100
|
Rated peak withstand current Ipk (KA)
|
220
|
Mechanical Characteristics
|
Overall height (mm)
|
2000
|
Number of vertical modules (functional height) 1 module = 50 mm
|
36
|
Depth (mm)
|
400/600 (front access) 800/1000(rear access)
|
Width of enclosure for devices (mm)
|
600 and 800
|
Width of busbar duct (mm)
|
200 (in 800 mm wide enclosure)
|
Width of cable duct (mm)
|
300
|
Partitioning
|
Form 1, 2, 3b and 4b
|
IP
|
30 / 31 / 54
|
IK
|
07/ 08/ 10
|
Aplicable standards
|
Type test
|
IEC61439-1
|
Insulation materials inside of enclosures
|
IEC60695
|
Environment conditions
|
Operation
|
Indoor
|
Altitude max. (m)
|
2000
|
Temperature average (°C)
|
35 °C
|
Degree of pollution
|
3
|
Others
|
Enclosure materials
|
Sheet metal
|
Painting
|
Epoxy resin powder electrostatic sprayed
|
Colour
|
RAL 7047 (enclosure)
RAL 9022 (functional unit)
|
Insulation materials inside of enclosure
|
high-temperature withstand, combustion self-prevent
|